CK4L & CS4L Model
The Rod Type switch-disconnectors of type C4
are for indoor installation in air insulated switchgear. Their switching
capacity is sufficient to meet all the needs that occur under practical
operating conditions. In particular they are suitable for on and off
switch of:
- Transformers
- Capacitor banks
- Cables
- overhead lines
- open feeders and ring circuits under
load and load conditions
With the switch in
the off position there is always a visible isolating distance. The
sliding blade principle permits the switches to be constructed with low
overall depths. As they can be constructed with a very narrow profile,
they permit extremely compact panel designs.
|
Ratings (single level)
|

|
|
Rated voltage (kV)
|
12 - 24
|
|

|

|
|
Rated current (A)
|
400 - 1,250
|
|

|

|
|
Rated short-circuit making current (kA)
|
40 - 63
|
|

|

|
|
ICE (A)
|
100
|
|

|

|
|
√3 ICL (A)
|
43
|
|

|

|
|
Rated normal current with fuses, undelayed (A)
|
40 - 63
|
|